Whirlpool Ventilation Hood RH8330 User Manual

Installation Instructions and Use and Care  
RH8330 SERIES  
RH8336 SERIES  
Part No. 626763/883264 Rev. C  
IMPORTANT:  
Read and save  
these instructions.  
30" and 36"  
Range Hood  
IMPORTANT:  
Installer: Leave Installation Instructions  
with homeowner.  
Homeowner: Keep Installation Instructions  
for future reference.  
Save: Installation Instructions for electrical  
inspector’s use.  
Home  
Appliances  
 
Before you start...  
Product dimensions  
Your safety and the safety of others  
are very important.  
This range hood can be used  
for vented installations only.  
We have provided many important safety  
messages in this manual and on your appliance.  
Always read and obey all safety messages.  
30" model: 29-7/8"  
12"  
10"  
36" model: 35-7/8"  
This is the safety alert symbol.  
exhaust  
connection  
mounting  
holes  
This symbol alerts you to potential hazards  
that can kill or hurt you and others.  
All safety messages will follow the safety alert  
symbol and either the word “DANGER” or  
“WARNING”. These words mean:  
5"  
4-1/4"  
7"  
DANGER  
knockout for  
rectangular  
roof vent  
You can be killed or seriously injured if you  
don’t immediately follow instructions.  
1"  
1/4"  
WARNING  
rear of  
hood  
You can be killed or seriously injured if you  
don’t follow instructions.  
knockout for  
wall vent  
19-3/4"  
All safety messages will tell you what the potential  
hazard is, tell you how to reduce the chance of  
injury, and tell you what can happen if the  
instructions are not followed.  
1-3/8"  
Important: Observe all governing codes  
and ordinances.  
exhaust  
connection  
mounting  
holes  
7-1/2"  
Proper installation is your responsibility.  
Make sure you have everything necessary  
for correct installation. It is the responsibility  
of the installer to comply with the  
clearances specified.  
1-3/8"  
Check the location where the range hood  
will be installed. The location should be  
away from strong draft areas, such as  
windows, doors, and strong heating vents.  
A 115-volt, 60-Hz, AC-only, fused  
WARNING — TO REDUCE THE RISK OF FIRE,  
ELECTRIC SHOCK, OR INJURY TO PERSONS,  
OBSERVE THE FOLLOWING:  
A.  
electrical supply is required. The total  
ampere load used, including the range  
hood, must not exceed 90% of the rated  
capacity of the circuit. The ampere rating  
of the range hood is located on the  
model/serial number rating plate located  
on the side cover of the blower motor  
housing.  
Use this unit only in the manner intended by  
the manufacturer. If you have questions,  
contact the manufacturer. Before servicing  
or cleaning unit, switch power off at service  
panel and lock switch power off at service  
panel and lock service panel to prevent  
power from being switched on accidentally.  
When the service disconnecting means  
cannot be locked, securely fasten a  
prominent warning device such as a tag to  
the service panel  
Tools and materials  
needed for  
installation  
The range hood must be  
connected with copper wire only.  
B.  
• compass or 7"  
circle template  
• pliers  
• 1-1/4" drill bit  
• pencil  
• ruler  
CAUTION: For general ventilating use only.  
Do not use to exhaust hazardous or explosive  
materials and vapors.  
• level  
• caulking gun  
• saber saw  
• keyhole saw  
• duct tape  
• Phillips screwdriver  
• metal snips  
• drill  
C.The range hood can be  
connected directly to the fused disconnect  
(or circuit breaker) box through flexible  
armored or nonmetallic sheathed copper  
cable. A U.L.-listed strain relief must be  
provided at each end of the power supply  
cable. Wire sizes (COPPER WIRE ONLY) and  
connections must conform with the rating  
of the appliance as specified on the  
model/serial rating plate.  
WARNING — TO REDUCE THE RISK OF A  
RANGE TOP GREASE FIRE:  
Mobile home installation  
Never leave surface units unattended at  
high settings. Boilovers cause smoking and  
greasy spillovers that may ignite. Heat oils  
slowly on low or medium settings.  
The installation of this range hood must  
conform to the Manufactured Home  
Construction Safety Standards, Title 24 CFR,  
Part 328 (formerly the Federal Standard for  
Mobile Home Construction and Safety, Title  
24, HUD, Part 280) or when such standard is  
not applicable, the Standard for  
Manufactured Home Installation 1982  
(Manufactured Home Sites, Communities  
and Setups) ANSI A225.1/NFPA 501A, or  
latest edition, or with local codes.  
Always turn hood ON when cooking at high  
heat or when cooking flaming foods.  
For power cord connected installations, a  
U.L.-listed range hood cord-connection kit  
MUST be used. Note: Some models come  
with a factory installed 3 ft. long power  
cord having a 3-prong ground plug.  
Clean ventilating fans frequently. Grease  
should not be allowed to accumulate on fan  
or filter.  
Use proper pan size. Always use cookware  
appropriate for the size of the surface  
element.  
Wire sizes must conform to the requirements  
of the National Electrical Code ANSI/NFPA  
70 — latest edition*, and all local codes  
and ordinances.  
WARNING — TO REDUCE THE RISK OF INJURY  
TO PERSONS IN THE EVENT OF A RANGE TOP  
GREASE FIRE, OBSERVE THE FOLLOWING:  
Electrical  
WARNING — TO REDUCE THE RISK OF FIRE,  
ELECTRIC SHOCK, OR INJURY TO PERSONS,  
OBSERVE THE FOLLOWING:  
SMOTHER FLAMES with a close-fitting lid,  
cookie sheet, or metal tray, then turn off the  
burner. BE CAREFUL TO PREVENT BURNS. If the  
flames do not go out immediately, EVACUATE  
AND CALL THE FIRE DEPARTMENT.  
requirements  
Important: Observe all governing codes  
and ordinances.  
Installation work and electrical wiring must  
be done by qualified person(s) in  
accordance with all applicable Codes and  
Standards, including Fire Rated  
It is the customer’s responsibility:  
To contact a qualified electrical  
installer.  
To assure that the electrical  
installation is adequate and in  
conformance with National Electrical  
Code, ANSI/NFPA 70 — latest edition*,  
and all local codes and ordinances.  
If codes permit and a separate ground wire  
is used, it is recommended that a qualified  
electrician determine that the ground path  
is adequate.  
Do not ground to a gas pipe.  
Check with a qualified electrician if you are  
not sure range hood is properly grounded.  
NEVER PICK UP A FLAMING PAN — You may  
be burned.  
Construction. The combustion airflow  
needed for safe operation of fuel-burning  
equipment may be affected by this unit’s  
operation. Follow the heating equipment  
manufacturer’s guideline and safety  
standards such as those published by the  
National Fire Protection Association  
(NFPA),and the American Society of  
Heating Refrigeration and Air Conditioning  
Engineers (ASHRAE), and the local code  
authorities.  
DO NOT USE WATER, including wet dishcloths  
or towels — a violent steam explosion will  
result. Use an extinguisher ONLY if:  
You know you have a Class ABC extinguisher,  
and you already know how to operate it.  
The fire is small and contained in the area  
where it is started.  
The fire department is being called.  
When cutting or drilling into wall or ceiling,  
do not damage electrical wiring and other  
hidden utilities.  
You can fight the fire with your back to an  
exit.  
Do not have a fuse in the neutral or ground  
circuit.  
Ducted fans must always be vented to the  
outdoors.  
Copies of standards listed may be obtained from:  
* National Fire Protection Association  
Batterymarch Park  
WARNING — To reduce the risk of fire, use  
only metal ductwork.  
Quincy, Massachusetts 02269  
Panel A  
 
Horizontal wall venting  
Venting requirements  
Now start...  
Slide cardboard or hardboard under range  
before moving range across floor to  
prevent damaging floor covering.  
Cover countertop, cooktop or set-in range  
with a thick, protective covering to prevent  
damaging countertop.  
With range hood in kitchen.  
Venting system must terminate to the  
outside.  
Do not terminate the vent in an attic or  
other enclosed space.  
3-1/4" x 10"  
through the wall  
wall cap  
Do not use four-inch laundry-type wall  
caps.  
Do not use plastic vent.  
Vent system needed for installation is not  
included.  
Determine which venting method,  
66"  
1.  
roof or wall hood venting, you  
It is recommended that the wall or roof cap  
used have a backdraft damper. If it does,  
remove the damper from the range hood  
exhaust connection supplied with the hood.  
need to use. The range hood comes  
shipped for venting through the roof.  
Determine which outside venting method  
you need to use.  
Disconnect and move  
2.  
freestanding range from cabinet  
Figure 3  
opening to provide easier access to upper  
cabinet and rear wall. Put a thick,  
protective covering over cooktop, set-in  
range or countertop to protect from  
damage or dirt. A protective covering will  
also be needed to set range hood on while  
getting it ready for installation.  
The length of the vent system and number  
of elbows should be kept to a minimum to  
provide efficient performance. The size of  
the vent system should be uniform. Do Not  
install two elbows together. Use duct tape  
to seal all joints in the vent system. Vent  
system can terminate either through the  
roof or wall. Use caulking to seal exterior  
wall or roof opening around exhaust hood.  
For the most efficient and quiet operation, it  
is recommended that the range hood be  
vented vertically through the roof using 7"  
round vent system.  
Recommended roof venting  
roof cap  
7" min. diameter  
round vent  
Flexible metal vent is Not recommended. If it  
is used, calculate each foot of flexible  
metal vent as two feet of straight metal  
vent. Flexible metal elbows count twice as  
much as standard elbows. Use metal  
ventwork only.  
3-1/4" x 10" to round  
vent transition  
Figure 4  
Recommended vent system lengths  
for venting an electric indoor grill  
Figures 1-4 show common venting methods  
and what types of materials are needed.  
Indoor electric grills produce more smoke  
than normal cooking and require at least  
410 CFM to provide adequate ventilation.  
centerline  
Vertical roof venting  
roof cap  
Horizontal wall venting  
Determine and clearly mark a  
vertical centerline on the wall and  
cabinet in the area the vent opening will  
be made.  
Use maximum of two feet of 3-1/4" x 10"  
vent with a wall cap and a free discharge  
area of 66 square inches. There should be  
no elbows in vent system between range  
hood and wall cap.  
3.  
7" round  
through roof  
damper located  
as far from hood  
as possible  
Vertical roof venting  
Use maximum of four feet of 3-1/4" x 10"  
vent terminating with a roof cap and with  
a free discharge area of at least 66 square  
inches.  
7-1/2"  
If longer vent system is required, the  
shortest possible ventwork length should be  
used to ensure the maximum CFM of air  
movement for best venting. A transition to  
round must be used as close to the hood  
as possible to eliminate the restriction  
caused by 3-1/4" x 10" vent. 45° elbows  
should be used instead of 90° elbows  
wherever possible. A roof cap providing a  
free area of 113 square inches is  
66"  
1-3/8"  
(from  
wall)  
Figure 1  
centerline  
recommended.  
Vertical roof venting  
Check the length of vent system used with  
lengths given in the chart to make sure  
vent system length does not exceed static  
pressure of .25.  
To wire through top, mark a line  
roof cap  
4.  
7-1/2" from the right of the  
centerline on the underside of the cabinet.  
Mark the point on this line that is 1-3/8" from  
back wall. Drill a 1-1/4" diameter hole  
through the cabinet at this point. Note: If a  
cord-connection kit is used, drill a 1-5/8"  
diameter hole.  
Static pressure vs. vent system length  
3-1/4" x 10"  
through the roof  
Equivalent vent system length (ft.)  
Static  
CFM  
460  
440  
417  
390  
355  
7" dia.  
10  
8" dia. 9" dia.  
pressure  
.06  
3-1/4" x 10"  
19  
31  
47  
62  
78  
12  
6
34  
56  
4
7
17  
.10  
3-1/4" x 10"  
damper  
25  
83  
.15  
11  
15  
18  
5
33  
111  
.20  
42  
.25  
11  
14  
7
90° elbow  
45° elbow  
66"  
5-1/2  
2-1/2  
1-3/8"  
7-1/2"  
Figure 2  
centerline  
To wire through rear, mark a line 7-1/2" from  
the right of the centerline on the wall. Mark  
the point on this line that is 1-3/8" from  
underside of cabinet. Drill a 1-1/4" diameter  
hole through wall at this point.  
Panel B  
 
Numbers correspond  
to steps.  
13. 13a.  
16. 16a.  
12.  
10. 10a.  
11. 11a.  
Remove the screw  
holding the terminal  
box cover. Remove  
cover.  
WARNING  
Excessive Weight Hazard  
Use two or more people to move and  
install range hood.  
Failure to follow this instruction can  
result in back or other injury.  
12. 12a.  
17. 17a.  
18. 18a.  
7. 8. 9.  
keyhole slot  
cabinet cutouts  
Remove three screws that  
8.  
hold light cover panel in place.  
Remove light panel and set aside.  
13.  
Lift the range hood into final position and  
center. Mark on the underside of cabinet  
the location of the four keyhole mounting  
slots and the wiring knockout. On some  
cabinets, filler blocks may need to be  
added for range hood to attach to cabinet.  
Set range hood aside on a protected  
surface.  
5-1/4"  
wire retainer  
indents  
5"  
1"  
5-1/4"  
wire  
retainer  
Do Not turn on power until  
To vent through the roof with  
14.  
installation is complete. Run  
5.  
3-1/4" x 10" rectangular vent, mark  
wiring through wall or cabinet according to  
the National Electrical Code and local  
codes and ordinances.  
blower wiring  
connector plug  
a line 1" and 5" from the back wall on the  
underside of the cabinet. Mark lines 5-1/4"  
to the right and left of the centerline on the  
underside of cabinet that connect the lines  
just drawn. Use a keyhole saw or saber saw  
to cut a rectangular opening for the vent  
system. Repeat for the underside of the top  
of the cabinet.  
remove  
screw  
keyhole slot  
outline  
Carefully disconnect blower wiring  
connector from terminal box  
connector plug. Snap blower wire retainer  
out of blower housing. Carefully set blower  
on protective covering.  
9.  
To vent through wall with 3-1/4" x 10"  
rectangular vent, measure 1/8" and  
3-5/8" down from underside of cabinet and  
mark on back wall. Measure and mark a  
line 5-1/4" to right and left of centerline,  
connecting the two lines. Use a keyhole saw  
or saber saw to cut a rectangular opening  
for the vent system.  
screw  
Note: It is much easier to remove the vent  
knockouts and to install the range hood  
with the blower removed.  
Start screws into neck area of  
each of the four keyhole  
mounting screw slots marked on the  
cabinet bottom.  
15.  
Venting through  
Lift range hood into position,  
To vent through the roof with round vent, a  
3-1/4" x 10" to round transition piece must  
be used.  
the roof  
16.  
and feed electrical wire  
roof vent  
through wiring opening. Position the range  
hood so that the large end of the keyhole  
slots are over the screws. Then push the  
range hood toward the wall so that the  
screws are in the neck of the keyhole slots.  
Tighten mounting screws to cabinet,  
making sure mounting screws are in narrow  
neck of slots. Make sure that damper blade  
rotates up and down freely.  
knockout  
Install vent system through the  
6.  
vent opening in upper cabinet or  
wall. Complete venting system according  
to method needed. See Venting  
requirements. Use caulking to seal exterior  
wall or roof opening.  
wiring knockout  
holes  
wiring knockout  
Remove the roof vent  
10.  
knockout. Remove top or rear  
terminal box  
3"  
wiring knockout as needed.  
damper blade  
(remove if roof cap  
has damper blade)  
5"  
screws  
filters  
Set range hood on protective  
Attach exhaust vent  
Reinstall blower back into  
7.  
cover. Insert finger into hole in filter  
11.  
connection to range hood.  
17.  
position. Snap blower wire  
and pull back and down to remove.  
Repeat for other filter.  
Check that the damper blade rotates up  
and down freely, if used.  
retainer back into blower housing indents.  
Reconnect the blower wiring connector  
back into the terminal box connector plug.  
Panel C  
 
Do Not turn on power until  
installation is complete.  
Venting through  
the wall  
WARNING  
14a.  
Run wiring through wall or cabinet  
according to the National Electrical Code  
and local codes and ordinances.  
keyhole slot  
outline  
Electrical Shock Hazard  
Disconnect power before making  
electrical connections.  
wiring knockout  
Connect ground wire to green ground  
screw in terminal box.  
screw  
Start screws into neck area  
Failure to do so can result in death or  
electrical shock.  
15a.  
of each of the four  
wall vent  
knockout  
keyhole mounting screw slots marked on  
the cabinet bottom.  
wiring knockout  
to light  
ground  
wires  
bulbs  
Lift range hood into final  
Remove the wall vent  
knockout and the inner  
knockout behind it. Remove top or rear  
wiring knockout as needed.  
16a.  
position, feeding electrical  
10a.  
wire through wiring opening. Position the  
range hood so that the large end of the  
keyhole slots are over the screws. Then push  
the hood toward the wall so that the  
screws are in the neck of the slots. Tighten  
mounting screws to cabinet, making sure  
mounting screws are in narrow neck of  
slots. Make sure that damper blade rotates  
up and down freely.  
terminal  
box  
connector  
damper blade  
blower  
wiring  
(remove if wall  
cap has damper  
blade)  
connector  
black wires  
11a.  
Attach the exhaust vent connection to the  
range hood. Check that the damper blade  
rotates up and down freely, if used.  
power  
white wires  
supply  
wiring  
twist-on  
connectors  
18.  
terminal box  
5"  
For models requiring direct wiring:  
12a.  
Connect white wiring from the terminal box,  
light harness and power supply wiring  
together with twist-on connector.  
Remove the screw  
holding the terminal  
box cover. Remove  
cover.  
Connect black wiring from the terminal box  
to power supply wiring with twist-on  
connector.  
3"  
Connect the power supply ground wire and  
the green ground wire inside the terminal  
box under the terminal box ground screw.  
WARNING  
Reinstall blower back into  
Use caulking to seal wire opening.  
Replace terminal box cover.  
17a.  
position. Snap blower wire  
Excessive Weight Hazard  
retainer back into blower housing indents.  
Reconnect the blower wiring connector  
back into the terminal box connector plug.  
Use two or more people to move and  
install range hood.  
For cord connected models:  
Failure to follow this instruction can  
result in back or other injury.  
WARNING  
keyhole slot  
Electrical Shock Hazard  
Plug into a grounded 3-prong outlet.  
Do not remove ground prong.  
Do not use an adapter.  
13a.  
Lift the range hood into final position and  
center. Mark on the underside of cabinet  
the location of the four keyhole mounting  
slots and the wiring knockout. On some  
cabinets, filler blocks may need to be  
added for range hood to attach to cabinet.  
Set range hood aside on a protected  
surface.  
Failure to follow these instructions can  
result in death, fire, or electrical shock.  
For your personal safety, this range hood  
must be grounded. To minimize possible  
shock hazard, the cord must be plugged  
into a mating, 3-prong, ground-type outlet,  
grounded in accordance with National  
Electrical Code, ANSI/NFPA 70 – latest  
edition* and all local codes and  
ordinances.  
If mating outlet is not available, it is the  
responsibility and obligation of the  
customer to have a properly grounded, 3-  
prong outlet installed by a qualified  
electrician.  
Do not use an extension cord.  
Using a U.L.-listed power supply  
cord-connection kit:  
Follow Power Cord Kit instructions for  
connecting wiring.  
Replace terminal box cover.  
19.  
Turn power supply on.  
Panel D  
 
Care of range hood  
Use & Care  
Information  
WARNING  
Filters:  
For best results, remove and clean often.  
Use this range hood only in the manner  
intended by the manufacturer. If you have  
any questions, contact the manufacturer.  
Before installation and before servicing or  
cleaning range hood, switch off power at  
service panel and lock service panel to  
prevent power from being switched on  
accidentally. When the service  
Electrical Shock Hazard  
Disconnect power before making  
electrical connections.  
Connect ground wire to green ground  
screw in terminal box.  
disconnecting means cannot be locked,  
securely fasten a prominent warning  
device, such as a tag, to the service panel.  
Failure to do so can result in death or  
electrical shock.  
to light  
Operation of  
range hood  
ground  
wires  
bulbs  
holes  
filters  
For best results, turn range hood fan on at  
beginning of cooking and allow it to run  
until all smoke and odors are removed from  
room.  
To remove aluminum filters:  
Place finger in hole. Pull back and down.  
To clean aluminum filters:  
Place filters in dishwasher or hot sudsy water  
to clean.  
terminal  
box  
To adjust fan speed:  
Turn fan speed control to desired setting  
between “Hi” and “Lo. Speed may be  
changed anytime during range hood  
operation.  
connector  
blower  
wiring  
To reinstall aluminum filters:  
connector  
Place edge of filter in channel opening so  
that side is above flange. Pull back. Press  
filter into position.  
black wires  
To turn range hood light “ON” and “OFF”:  
Turn light control to operate light “ON” or  
“OFF”. Light may be turned to “OFF” or  
“ON” anytime during range hood  
operation.  
When it's time to replace your  
aluminum filter:  
power  
white wires  
supply  
wiring  
twist-on  
1. Choose your filter order number.  
30" Hood Model RH8330:  
connectors  
“Night” light setting:  
Order Filter no. 883276  
Turn light control to “Night” setting when  
you need the light dimmed for use as a  
night light.  
18a.  
36" Hood Model RH8336:  
Order Filter no. 883277  
For models requiring direct wiring:  
Connect white wiring from the terminal box,  
light harness and power supply wiring  
together with twist-on connector.  
Connect black wiring from the terminal box  
to power supply wiring with twist-on  
connector.  
2. Call Whirlpool's Telesales line at  
1-800-442-9991  
3. Give the Telesales Representative the  
part number needed.  
4. The Representative will give you the  
current price.  
Connect the power supply ground wire and  
the green ground wire inside the terminal  
box under the terminal box ground screw.  
5. Place your order using your Master  
Card®, Visa® or Discover® credit card.  
6. If you wish: mail a check or money order  
to:  
Use caulking to seal wire opening.  
Replace terminal box cover.  
Whirlpool Corporation  
1900 Whirlpool Drive  
LaPorte, IN 46350-9980  
Attn: Accessory Accounting  
For cord connected models:  
WARNING  
7. Be sure to ask the Telesales  
Representative about the wide variety of  
other Whirlpool Product Accessories.  
Blower motor:  
Electrical Shock Hazard  
Plug into a grounded 3-prong outlet.  
Do not remove ground prong.  
Do not use an adapter.  
To clean blower motor:  
Clean exterior of motor with a damp cloth  
and grease-cutting detergent.  
Exterior surfaces:  
Clean the range hood with a mild  
detergent and soft cloth. Do Not use  
abrasive cleaners or steel wool.  
Failure to follow these instructions can  
result in death, fire, or electrical shock.  
For your personal safety, this range hood  
must be grounded. To minimize possible  
shock hazard, the cord must be plugged  
into a mating, 3-prong, ground-type outlet,  
grounded in accordance with National  
Electrical Code, ANSI/NFPA 70 – latest  
edition* and all local codes and  
Light:  
Do Not use bulbs larger than 60 watts  
in light sockets.  
To replace bulbs:  
Remove three screws that hold light cover  
panel in place. Remove panel and set  
aside. Replace bulb.  
ordinances.  
If mating outlet is not available, it is the  
responsibility and obligation of the  
customer to have a properly grounded, 3-  
prong outlet installed by a qualified  
electrician.  
Replace light cover panel before operating  
fan or light.  
Light bulbs are not included.  
Do not use an extension cord.  
Using a U.L.-listed power supply  
cord-connection kit:  
Follow Power Cord Kit instructions for  
connecting wiring.  
Replace terminal box cover.  
19a.  
Turn power supply on.  
Copies of standards listed may be obtained from:  
* National Fire Protection Association  
Batterymarch Park  
Quincy, Massachusetts 02269  
Panel E  
 
If range hood does  
not operate...  
If you need  
service...  
If you need  
assistance...  
In the event your Whirlpool appliance  
should need service, call the dealer from  
whom you purchased the appliance or a  
Whirlpool-authorized service company. A  
Whirlpool-authorized service company is  
listed in the Yellow Pages of your phone  
directory under “Appliance — Household —  
Major — Service or Repair.” You can also  
obtain the service company’s name and  
number by dialing, free, within the  
The Whirlpool Consumer Assistance Center  
will answer any questions about operating  
or maintaining your range hood not  
Check that the circuit breaker is not tripped  
or the house fuse blown.  
covered in the Installation Instructions. The  
Whirlpool Consumer Assistance Center is  
open 24 hours a day, 7 days a week. Just  
dial 1(800) 253-1301 — the call is free.  
®
Whirlpool Range Hood Warranty  
continental United States, the Whirlpool  
Consumer Assistance Center number,  
1(800) 253-1301.  
LENGTH OF WARRANTY  
WHIRLPOOL WILL PAY FOR  
FSP® replacement parts and repair labor to correct  
defects in materials or workmanship. Service must  
be provided by an authorized WhirlpoolSM service  
company.  
FULL ONE-YEAR WARRANTY  
Maintain the quality built into your Whirlpool  
appliance — call a Whirlpool-authorized  
service company.  
From date of purchase  
WHIRLPOOL WILL NOT PAY FOR  
A. Any labor costs incidental to the replacement of defective parts.  
B. Consumable parts such as light bulbs and filters.  
C. Service calls to:  
1. Correct the installation of the range hood.  
2. Instruct you how to use the range hood.  
3. Replace house fuses or correct house wiring.  
D. Repairs when range hood is used in other than normal, single-family household use.  
E. Pickup and delivery. This product is designed to be repaired in the home.  
F. Damage to range hood caused by accident, misuse, fire, flood, act of God or use of  
products not approved by Whirlpool.  
WHIRLPOOL CORPORATION SHALL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some  
states do not allow the exclusion or limitation of incidental or consequential damages so this limitation or  
exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have  
other rights which vary from state to state.  
Outside the United States, a different warranty may also apply. For details, please contact your  
franchised Whirlpool distributor or military exchange.  
CORPORATION  
Part No. 626763/883264 Rev. C  
© 2000 Whirlpool Corporation  
® Registered Trademark/SM Trademark of Whirlpool, U.S. A.  
Benton Harbor, Michigan 49022  
 
Printed in U.S.A.  

Weslo Home Gym WLEX27181 User Manual
West Bend Griddle L5749 User Manual
Whirlpool Air Conditioner ACE082XP1 User Manual
Whirlpool Microwave Oven GH4155XPS1 User Manual
White Rodgers Welding System 37 6349A User Manual
Windsor Vacuum Cleaner CS24 10060210 User Manual
Wolf Appliance Company Ventilation Hood PL341912 User Manual
Woodstock Nail Gun W1775 User Manual
Zanussi Cooktop GC 21 M User Manual
Zanussi Range 200109 User Manual